Honeywell T775E1056 Process Controller – T775 Series
Honeywell T775E1056 is listed for T775 Series RFQ review. Confirm quantity, condition and destination before quotation.
Model: CC-PDIL51 CC-PDOD51 CC-PAIH51 CC-PAOH51
Product Overview
Commercial availability is handled through direct RFQ, model verification and export-oriented follow-up rather than public cart checkout.
Datasheet Preview
Use attached product manuals when available. If the manual is not public yet, request the full file directly through RFQ.
Commercial Path
Product pages on DRIVEKNMS are designed to verify model, brand and series first, then move the buyer into one clean quotation path.
Technical Dossier
The CC-P I/O module family was introduced alongside the Experion PKS R100 release in the early 2000s as a replacement for the legacy TDC 3000 and PlantScape I/O infrastructure. The original CC-P modules operated on the FTE (Fault Tolerant Ethernet) backbone and communicated via the C300 Controller's IOTA (I/O Termination Assembly) backplane. Early revisions (Rev A/B) supported single-ended wiring configurations only. Subsequent hardware revisions introduced differential input support, extended temperature ratings (–40°C to +70°C for select models), and improved EMI shielding for use in electrically noisy environments such as motor control centers.
With the Experion PKS R400 and R500 software releases, Honeywell introduced the Series C I/O architecture (CC-IP/CC-OP series), which offers higher channel density and HART 7 pass-through. However, the CC-P series remains in active production and is fully supported under Honeywell's Extended Lifecycle Support (ELS) program through at least 2030. Plants running Experion R210 through R500 can operate CC-P modules without hardware replacement, though firmware compatibility must be verified against the specific Experion release matrix.
The following SKUs represent the verified CC-P series module catalog. Each entry is classified by I/O function type:
Digital Input (DI) Modules
CC-PDIL51: 24 VDC digital input, 32-channel, low-density IOTA mount
CC-PDIL01: 24 VDC digital input, 8-channel, single-ended, standard IOTA
CC-PDIS01: 120 VAC digital input, 8-channel, isolated, field-powered
CC-PDIS51: 120 VAC digital input, 32-channel, isolated, IOTA-mounted
CC-PDID01: 24 VDC digital input, 8-channel, dry contact, intrinsically safe rated
Digital Output (DO) Modules
CC-PDOD51: 24 VDC digital output, 32-channel, sourcing type, IOTA mount
CC-PDOD01: 24 VDC digital output, 8-channel, sourcing, standard IOTA
CC-PDOS01: 120 VAC digital output, 8-channel, triac isolated, field-powered
CC-PDOS51: 120 VAC digital output, 32-channel, triac isolated, IOTA-mounted
CC-PDOR01: Relay digital output, 8-channel, Form C contacts, 2A per channel
Analog Input (AI) Modules
CC-PAIH51: 4–20 mA analog input, 16-channel, HART-enabled, high-density IOTA
CC-PAIH01: 4–20 mA analog input, 8-channel, HART pass-through, standard IOTA
CC-PAIC01: Thermocouple/RTD analog input, 8-channel, cold junction compensated
CC-PAIM01: Millivolt analog input, 8-channel, high-resolution 16-bit ADC
CC-PAIX01: Analog input, 8-channel, configurable 0–10V / 4–20 mA, isolated
Analog Output (AO) Modules
CC-PAOH51: 4–20 mA analog output, 16-channel, HART-enabled, high-density IOTA
CC-PAOH01: 4–20 mA analog output, 8-channel, HART pass-through, standard IOTA
CC-PAOC01: 0–10 VDC analog output, 8-channel, voltage sourcing, isolated
Power & Communication Accessories
CC-PCF901: C300 Controller module, primary CPU, Experion PKS FTE interface
CC-TCNT01: FTE network interface card, dual-port, redundant Ethernet backbone
CC-P modules incorporate a proprietary backplane communication protocol that requires functional validation beyond standard power-on testing. DriveKNMS applies a multi-stage verification process to all CC-P inventory:
Continue The Model Path
Move from this exact model into the matching system hub, brand archive, model-family archive or lifecycle sourcing route before sending a final RFQ list.